General technical data
Original instruction manual Date: 2017.08.28 Page 25 of 28
16.4
Contact outputs at at SAFELINE
ZMB,ZMK, ZMT RM 230 KM
Output design
Output 13/14, 23/24 13/14 – 83/84 13/14 – 83/84 O1-O4
Minimal switch current 10mA 10mA 10mA 10mA
Switching capacity according to
DIN EN 60947-4-1/ EN 60947-5-1
DC1: 24V/ 6A
DC13: 24V/ 5A
0,1Hz
DC1: 24V/ 6A
DC13: 24V/ 5A
0,1Hz
DC1: 24V/ 6A
DC13: 24V/ 5A
0,1Hz
Switching capacity according to
DIN EN 60947-4-1/ EN 60947-5-1
AC1:250V/ 6A
AC15: 230V/ 3A
AC1:250V/ 6A
AC15: 230V/ 3A
Sum of the switch and continuous
current
≤ 6A 13/14-43/44: ≤ 6A
53/54-83/84: ≤ 6A
13/14-43/44: ≤ 6A
53/54-83/84: ≤ 6A
0,4A
Electrical life
(1)
at DC13: 24V/ 1A 1x10
5
1x10
5
1x10
5
Electrical life
(1)
at DC13: 24V/ 4A 4x104 4x10
4
4x104
Electrical life
(1)
at AC15: 230V/ 1A 2x10
5
2x10
5
Electrical life
1)
at AC15: 230V/ 4A 8x10
4
8x10
4
Switch and continuous current Ω / L 0,1A
Mechanical contact life
(1)
> 10
7
> 10
7
> 10
7
> 2X10
6
Maximal switching cycles at DC13: 5A 360 cycles/h 360 cycles/h 360 cycles/h
Maximal switching cycles at AC15: 3A 360 cycles/h 360 cycles/h
Contact fuse 6A slow 6A slow 6A slow
Short circuit strength: Automat
safety fuse
1000A SCPD 6A
200A/ B6
800A/ 6A gG
1000A SCPD 6A
Rated insulation voltage 250V AC 250V AC
Impulse withstand voltage
Use in pollution degree 2 Environment.
4KV 4KV
Reaction time, drop out time 10ms 10ms 10ms 10ms