Troubleshooting guide
Heatpump models
operate
Select emergency heat mode
Thermostat in Unoccupied
mode
Select Override to force the thermostat Occupied
heating setpoint
Wait, the anticycling period will end and the
equipment will start
Heating setpoint is satisfied
Raise the Heating setpoint
High Balance point attained
1. Mode is locked out based on outside air
temperature
2. Change configuration parameter High BP to value
90 °F ( 32 °C ) to by-pass lockout
1. Mode is locked out based on outside air
temperature
2. Change configuration parameter H Lock to value
120 °F ( 49 °C ) to by-pass lockout
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RH & W1. The
heating should come ON. If it does not, verify wiring
and check if a jumper is required between RC & RH
operate in heating
Thermostat in Unoccupied
mode
Select Override to force the thermostat Occupied
heating setpoint
Wait, the anticycling period will end and the
equipment will start
Heating setpoint is satisfied
Raise the Heating setpoint
Low Balance point attained
1. Mode is locked out based on outside air
temperature
2. Change configuration parameter Low BP to value -
12 °F ( -24 °C ) to by-pass lockout
1. Mode is locked out based on outside air
temperature
2. Change configuration parameter H Lock to value
120 °F ( 49 °C ) to by-pass lockout
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RH & W1. The
heating should come ON. If it does not, verify wiring
and check if a jumper is required between RC & RH
configuration
1. Wrong selection of parameter Re Valve
2. Select O will energize the valve in cooling
operation. Valve is normally heat.
3. Select B will energize the valve in heating
operation. Valve is normally cool.