Installing and Operating Instructions
1592020010
1592020010 XR10CX GB m&M r1.1 05.03.2007.doc XR10CX 1/4
Digital controller with cooling or heating action
XR10CX
CONTENTS
1. GENERAL WARNING ___________________________________________________1
2. GENERAL DESCRIPTION _______________________________________________1
3. CONTROLLING LOADS _________________________________________________1
4. FRONT PANEL COMMANDS _____________________________________________1
5. MAX & MIN TEMPERATURE MEMORIZATION_______________________________1
6. MAIN FUNCTIONS _____________________________________________________2
7. PARAMETERS ________________________________________________________ 2
8. DIGITAL INPUT ________________________________________________________ 3
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS ___________________________3
10. X-REP OUTPUT – OPTIONAL ____________________________________________ 3
11. INSTALLATION AND MOUNTING _________________________________________ 3
12. ELECTRICAL CONNECTIONS ____________________________________________ 3
13. HOW TO USE THE HOT KEY_____________________________________________ 3
14. ALARM SIGNALS ______________________________________________________3
15. TECHNICAL DATA _____________________________________________________3
16. CONNECTIONS _______________________________________________________ 4
17. DEFAULT SETTING VALUES_____________________________________________ 4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and
quick reference.
The instrument shall not be used for purposes different from those described hereunder.
It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits
avoiding sudden temperature changes with high atmospheric humidity to prevent
formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be
opened.
In case of failure or faulty operation send the instrument back to the distributor or to
“Dixell S.p.A.” (see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far
enough from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1)
in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XR10C, format 32 x 74 mm format is a single stage temperature controller suitable for
applications in the field of refrigeration or heating. It provides a relay output to drive the
compressor. It is also provided with 2 NTC or PTC probe inputs, the first one for temperature
control, the second one, optional, to connect to the HOT KEY terminals to signal the
condenser temperature alarm or to display a temperature. The digital input can operate as
third temperature probe.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,
to a network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB
family. It allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily
programmed through the keyboard.
3. CONTROLLING LOADS
3.1 THE REGULATION OUTPUT
The regulation is performed according to the temperature measured by the probe.
The instruments are provided with the CH programmable parameter which enables the user to
set the regulation both for heating or cooling applications:
· CH = CL: cooling applications
· CH = Ht: heating applications
3.2 CH = CL: COOLING APPLICATIONS.
The Hy value is automatically set above the Set Point. If the temperature increases and
reaches set point plus differential the compressor is started and then turned off when the
temperature reaches the set point value again.
Time
Temper.
Compr.
SET
ON
3.3 CH = HT: HEATING APPLICATION.
The Hy value is automatically set under the Set Point. If the temperature decreases and
reaches set point minus differential the regulation output is activated and then turned off when
the temperature reaches the set point value again.
Time
Temper.
Heating
ON
SET
SET- HY
Time
4. FRONT PANEL COMMANDS
: To display target set point; in programming mode it selects a parameter or confirm
an operation.
(DEF) Not enabled
(UP): To see the max. stored temperature; in programming mode it browses the
parameter codes or increases the displayed value.
(DOWN) To see the min stored temperature; in programming mode it browses the
parameter codes or decreases the displayed value.
To switch the instrument off, if onF = oFF.
Not enabled
KEY COMBINATIONS:
+
To lock & unlock the keyboard.
+ To enter in programming mode.
+ To return to the room temperature display.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED MODE FUNCTION
ON Compressor enabled
Flashing Anti-short cycle delay enabled
ON An alarm is occurring
ON Energy saving enabled
°C/°F
ON Measurement unit
°C/°F
Flashing Programming phase
5. MAX & MIN TEMPERATURE MEMORIZATION
5.1 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the n key.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the n key again or by waiting 5s the normal display will be restored.
5.2 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the o key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the o key again or by waiting 5s the normal display will be restored.
5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1. Hold press the SET key for more than 3s, while the max. or min temperature is
displayed. (rSt message will be displayed)
2. To confirm the operation the “rSt” message starts blinking and the normal temperature
will be displayed.
Question and Answer IconNeed help?

Do you have a question about the dixell XR10CX and is the answer not in the manual?

dixell XR10CX Specifications

General IconGeneral
ModelXR10CX
TypeTemperature Controller
Resolution0.1 °C
Frontal ProtectionIP65
Control AlgorithmON/OFF
CertificationsCE, RoHS
Input TypeNTC
Display TypeLCD
Output TypeRelay
Storage Temperature-20 to +70 °C
Accuracy± 0.5 °C
Dimensions32 x 74 mm
Weight150 g

Summary

General Warning

Please Read Before Using This Manual

Important instructions to read before using the manual for easy reference and correct operation.

Safety Precautions

Essential safety measures to follow during installation, operation, and maintenance to prevent hazards.

General Description

Controlling Loads

The Regulation Output

Explanation of how the controller regulates based on probe temperature and the CH parameter for heating/cooling.

CH = CL: Cooling Applications

Description of cooling mode operation where the compressor activates based on setpoint and differential.

CH = HT: Heating Application

Description of heating mode operation where the output activates when temperature drops below setpoint plus differential.

Front Panel Commands

Use of LEDs

Explanation of the status and meaning of each LED indicator on the controller's front panel.

Max & Min Temperature Memorization

How to See the Min Temperature

Procedure to view the minimum recorded temperature using the 'down' key.

How to See the Max Temperature

Procedure to view the maximum recorded temperature using the 'up' key.

How to Reset the Max and Min Temperature Recorded

Steps to reset the stored maximum and minimum temperature values using the SET key.

Main Functions

How to See the Setpoint

Instructions to view the current setpoint value by pressing the SET key.

How to Change the Setpoint

Procedure to modify the setpoint value using the SET and arrow keys.

How to Change a Parameter Value

Steps to enter programming mode and modify parameter values using SET and arrow keys.

The Hidden Menu

Access and navigation details for the hidden menu containing advanced parameters.

How to Lock the Keyboard

Steps to lock the front panel keypad using the UP + DOWN keys to prevent accidental changes.

To Unlock the Keyboard

Procedure to unlock the front panel keypad using the UP + SET keys.

The ON/OFF Function

How to turn the instrument on and off using the ON/OFF key, and its effect on regulation.

Parameters

Regulation

Parameters related to temperature regulation, including differential, minimum, and maximum set points.

Display

Parameters affecting the unit of measurement, display resolution, and update delay.

Alarms

Parameters for configuring temperature alarms, their recovery, and delay times.

Condenser Temperature Alarm

Parameters for managing alarms related to condenser temperature, including low/high limits and recovery.

Digital Input

Configuration parameters for the digital input, including polarity, function, and alarm delays.

Other

Miscellaneous parameters like serial address, probe type, and display options.

Digital Input

Door Switch Input (i1F = dor)

Configuration for the door switch function, including status signaling and alarm delay.

Generic Alarm (i1F = EAL)

Setup for a generic external alarm, its delay, and how it affects the unit.

Serious Alarm Mode (i1F = bAL)

Configuration for a serious external alarm, its delay, and output behavior.

Pressure Switch (i1F = PAL)

Setting for pressure switch function, activation count, and alarm conditions.

Inversion of the Kind of Action: Heating-Cooling (i1F = Htr)

Function to invert the controller's action between heating and cooling modes.

Energy Saving (i1F = ES)

How the energy saving function modifies the setpoint when the digital input is activated.

Digital Inputs Polarity

Setting the polarity for the digital input, determining activation by opening or closing contacts.

TTL Serial Line - For Monitoring Systems

X-REP Output – Optional

Installation and Mounting

Electrical Connections

Probe Connection

Recommendations for installing and connecting the temperature probes for accurate measurements.

How to Use the Hot Key

How to Program a Hot Key from the Instrument (Upload)

Procedure to upload controller configuration parameters to a Hot Key device.

How to Program an Instrument Using a Hot Key (Download)

Procedure to download parameters from a Hot Key device to program the instrument.

Alarm Signals

Alarm Recovery

Information on how different types of alarms (probe, temperature, external, pressure) are recovered.

Other Messages

List and explanation of other messages that may appear on the instrument display.

Connections

XR10CX-8A Compressor

Wiring diagram and connections for the XR10CX with an 8A compressor.

XR10CX - 20A Compressor

Wiring diagram and connections for the XR10CX with a 20A compressor.

Default Setting Values

Related product manuals