Why DKS 6500 operator will not run, but the power LED is ON?
- LlambertcharlesAug 19, 2025
If the DKS Gate Opener operator doesn't run but the power LED is ON, ensure at least one external entrapment protection device is connected in each entrapment area, and the UL 325 DIP-switches are ON. Test by pushing the test button or momentarily jumpering terminal 1 to terminal 2 (or 1 to 5). If the input LED doesn't light up, check the terminal strip or replace the circuit board. If the LED lights up, check the motor by removing the circuit board and, with power ON, momentarily jumpering terminal 19 to terminal 18, and then terminal 19 to terminal 17 using a 14 AWG insulated jumper wire (CAUTION – HIGH VOLTAGE). If the motor runs in both directions, replace the control board. If it doesn't run, the issue could be a bad motor, motor capacitor, wiring, or a bad control board.