16
EN
Operation Elite Control
7.4.2 Selecting a Parameter
The following table describes the parameters available
for the Elite Control.
Parameter Name DX CW Factory Default Parameter Range
P-1 High Fan Limit
x x 95 51–95
Select a higher number to increase the fan speed, a lower number to decrease the fan speed.
I
The 35-95 parameter range setting is applicable to soware revision #B24 and newer.
P-2 Low Fan Limit
x x 50 30–50
Select a higher number to increase the fan speed, a lower number to decrease the fan speed.
P-3
Compressor Staging
Time Delay
x 15 5–135 seconds
Use for installations where more than one system operates from the same power source. Different
staging delays allow compressors to start at different times when the power is interrupted. Stage the
units at least five seconds apart.
P-4
Inside Air Temperature
Sensor Calibration
x x Ambient Temperature Ambient Temperature ±10°F (6°C)
Calibrate the sensor to display the correct room temperature reading.
The setting increments are in °F even when the control is set to display °C.
P-5 Failsafe Level
x 3
0 = Minimal Protection
1
1 = Continuous No Display
2
2 = Continuous With Display
2
3 = Four Failures, Reset Required
I
1
Part of the functionality of this setting is only applicable to soware revision #C40 and newer.
2
The setting is applicable to soware revision #C39 and older.
Refer to “Fail Safe Levels” on page 23.
P-6 Low Voltage Monitor
x OFF OFF, 95 VAC/195 VAC
Set the built-in voltmeter circuit that monitors the AC input voltage prior to each cooling or heating
cycle when set to 95 VAC or 195 VAC.
• For 100–120 VAC input power, set to OFF or 95.
• For 208–240 VAC input power, set to OFF or 195.
I
The setting is applicable to soware revision #A15 and newer.