Dräger Flame 3000
3.3 Commissioning and functional testing
1. Switch on the Dräger Flame 3000.
NOTICE
When switched on, the Dräger Flame 3000 will perform an
internal test and system initialization that takes approximately
ve seconds.
2. Test the Dräger Flame 3000 using a ame simulator (refer to the
ame simulator instructions for details; Dräger recommend the
Dräger FS-5000). The status LED will turn red when it detects the
simulated ame.
Failure of the Dräger Flame 3000 to respond to the ame simulator
should be reported to Dräger.