3.3 Commissioning and functional testing
1. Switch on the Dräger Flame 3000.
NOTICE
When switched on, the Dräger Flame 3000 will perform an
internal test and system initialization that takes approximately
ve seconds.
2. Test the Dräger Flame 3000 using a ame simulator (refer to the
ame simulator instructions for details; Dräger recommend the
Dräger FS-5000). The status LED will turn red when it detects the
simulated ame.
Failure of the Dräger Flame 3000 to respond to the ame simulator
should be reported to Dräger.