Dräger Flame 3000
2.3 Intended use
The Dräger Flame 3000 is intended for use in areas that may contain
a potentially explosive atmosphere (see Section 2.5 for details of the
explosive environments in which the Dräger Flame 3000 can be used).
It is used to monitor an area and trigger the necessary control actions
upon the detection of re or ame within its eld of view.
2.4 Limitations on use
The Dräger Flame 3000 is not approved for use in oxygen-
enriched atmospheres.
As the Dräger Flame 3000 responds to visible ame, it cannot be
used in locations where are stacks and other open ames are
within its eld of view without triggering false alarms.
The Dräger Flame 3000 is unable to detect res that are invisible
to the naked eye, such as those using pure hydrogen, methanol
and sulphur as fuel.
The sensitivity of the Dräger Flame 3000 to ame is reduced by
obscurants such as smoke, fog and other airborne particulates.
The Dräger Flame 3000 may be blinded by extremely dense
obscurants.
Although the Dräger Flame 3000 is insensitive to arc welding, arc
welding should not take place within 1 m of the ame detector.
2.5 Approvals
ATEX: Certicate number FM07ATEX 0033, II 2 G Ex db IIC T4
IECEx: Certicate number FME 07.0002, II 2 G Ex db IIC T4
FM: Class I Div 1 Groups B, C, D, T4, ambient: -60 °C to +85 °C; Class
I Zone 1 AEx/Ex db IIC T4, ambient: -60 °C to +85 °C
CE: GEC EN55022 & 082
2.6 Explanation of type-identifying marking and
symbols
The Dräger Flame 3000 is tted with a label that shows the certication
and conditions within which it can operate.
TYPE: FLAME 3000
SERIAL No:
YEAR:
AMBIENT: - 60ºC +85ºC
AMBIENT: - 60ºC +85ºC
FM07ATEX 0033
IECEx FME 07.0002
Maximum Voltage: 30VDC
Maximum Current: 250mA
TYPE 4, IP66
Class I DIV 1 GROUPS B,C,D,T4
AMBIENT: - 60ºC +85ºC
Class I Zone 1 AEx/Ex db IIC T4
AMBIENT: - 60ºC +85ºC
DO NOT REPAIR FLAME PATHS
SEAL CONDUIT WITHIN 18" OF ENCLOSURE ENTRANCE
2809
II 2 G Ex db IIC T4
3260
ENTRY:
½" NPT
¾" NPT
Single
Dual
M25
M20
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT WARNING: REFER TO FLAME 3000 TECHNICAL MANUAL BEFORE INSTALLING OR MAINTAINING THIS UNIT
Draeger Safety U.K. Limited, Blyth,
Northumberland, NE24 4RG
, U.K.
Manufactured by: Micropack Engineering
Aberdeen, Scotland, AB12 4RR
3879