10
Dräger Flame 3000
3.2 Installation
WARNING
Do not open the enclosure in an explosive atmosphere as it
could lead to an explosion.
Ensure that the ame path of the Dräger Flame 3000 is not
damaged during installation. A damaged ame path could
lead to an explosion.
Do not drill holes in the enclosure as it could lead to an
explosion.
CAUTION
The Dräger Flame 3000 may be damaged by high voltage
insulation tests and other cable testing operations. It should
only be installed after these tests are complete.
Do not drop or knock the enclosure as this may damage the
detector assembly.
Only appropriately trained service personnel may open the
enclosure. Incorrect disassembly of the Dräger Flame 3000
may damage the equipment.
NOTICE
Before installing the Dräger Flame 3000 it is advisable to
check the mounting locations to ensure that there have been
no changes made during construction that will affect detector
coverage.
!
!
i
i
3.2.1 Mechanical
The mounting bracket allows the vertical orientation of the Dräger
Flame 3000 to be adjusted from 0 to 45°, and allows a horizontal
rotation of up to 90°.
3883