Annex
14.3.5 Channel types
14.3.6 Structure of the state register of REGARD 7000 channels
313101…337676 332C…932B F32 12288 A1 to A8 alarm thresholds for
1536 REGARD 7000 chan-
nels.
337701…340772 9344…9F43 F32 1536 Measurement range underruns
for 1536 channels
340801…343872 9F60…AB5F F32 1536 Measurement range overruns
for 1536 channels
343901…348508 AB7C…BD7
B
U8 9216 Measurement units for 1536
REGARD 7000 channels
348601…357816 BDD8…E1D7 U8 18432 Gas names for 1536 REGARD
7000 channels.
357817…362424 E1D8…F3D7 U8 9216 Short gas names for 1536
REGARD 7000 channels.
362465…365536 F400…FFFF U32 1536 Output states for 1536 chan-
nels (available depending on
type). For further information,
see the following chapter:
"Structure of output state
information", page 154
Register (dec.) U16 address Type Num-
ber
Contents
Value REGARD 7000 channel type
0x0000 Channel not present
0x0101 4-20 mA Input Module / 4-20 mA Input Module HART®
0x0103 Digital Input Module
0x0104 Bridge Input Module
0x0107 Modbus RTU Master Module
0x0141 Relay Output Module
0x01D0 Gateway Output Module
0x01D1 Gateway Output PROFIBUS
0x01D2 Gateway Output PROFINET
Bit address Bit value (mask) Type Contents
0.0 1 U1 Activation state (1 = active channel, 0 =
inactive channel)
0.1 2 U1 Online system test (currently only
implemented for the relay module
channel)
0.2 4 U1 Inhibit (1 = active)
0.3 8 U1 Channel present (1 = present)
0.4 16 U1 Timeliness of data packet (1 = current,
data packet max. 3 s old)
0.5 32 U1 Timeliness of configuration (1 = cur-
rent, config. info. max. 90 s old)