7.7 User role concept
REGARD 7000 has a function and rights management oriented to user roles.
Individual users can be created and must be assigned one of 5 roles.
Corresponding higher-level functions and rights are available for selecting the role.
Multiple users can be assigned to one role. Access to the system is protected by
individual passwords for all users.
All controls that are not available for a specific role are hidden.
After 15 minutes of inactivity the user is logged out or the screen is locked. The user
must log in again. If an input from the user is expected during the locked period
(e.g. during configuration), the user will be prompted to enter the user password
again. If automatic login is configured for the dashboard Dashboard (For further
information, see the following chapter: "Set automatic login", page 118), the
configured user is automatically logged in.
Dräger recommends assigning the Configuration, Maintenance and
Administration roles to appropriately trained users only.
7.7.1 View only role
The following functions are available:
Measured value displays
Status displays
Change your password
7.7.2 Operation role
The following additional functions are available for the View only role:
View detailed information on individual channels.
View saved system documents (only if additional functionality is enabled,
optionally available).
Acknowledge of alarms and special signals.
7.7.3 Maintenance role
The following additional functions are available for the Operation role:
Display information on system components.
Display channel configuration.
Generate documentation of system configuration as PDF file (only if additional
functionality is enabled, optionally available).
Prepare system for adjustment of the connected transmitters (such as setting
channels to the Inhibit state).
Test REGARD 7000 system components.
7.7.4 Configuration role
The following additional functions are available for the Maintenance role:
Run system configuration.
Make Dashboard settings.