Error overview
MPA 41xx PF
Error
ID
Internal
error
Error description
0x18
ERROR FROM EXTERNAL APPLICATION
Possible cause of the error:
Timeout of parameter mode/manual mode (0.5 h without pressing a key) - detail error 4. Byte =
0xA0
An invalid eldbus address has been entered in P11 for the connected bus module.
Detail error 4. Byte = 0xA1 and 6. Byte = set address P11
Additional byte 1: 0xB4 (error of the VisionBox)
Switch-o was caused externally by selecting the
"switch-o" function in the PC software of the VisionBox
Additional byte 1: 0x90 (internal MPA error P2)
Additional byte 4: 0x01 Internal error
Additional byte 4: 0x08 Internal error
Additional byte 4: 0x09 Internal error
Additional byte 4: 0x0C Error conguration with 5. Byte=0x13:
6. Byte = parameter of allocation number, e.g. 0x13 = P19
7. Byte = parameter value of low byte
8. Byte = parameter value of high byte
Error conguration with 5. Byte = 0x14:
Heat request via HW input (P17=0) and air purge
has priority over heat request
(P241: Bit 0=1) not possible
Additional byte 4: 0x16 Internal error
Additional byte 4: 0x1D Internal error
Additional byte 4: 0x1E Internal error
Additional byte 4: 0xE8 Extension module not recognized
Additional byte 4: 0xEE Interruption of communication to the MPA
Additional byte 4: 0xEF Extension module not compatible with the MPA version
Additional byte 4: 0xA0 Timeout parameterisation mode
Additional byte 4: 0xA1 Invalid bus address
Additional byte 4: 0xA2 Error parameter adjustment of the service box
Additional byte 4: 0xA5 The extension module does not respond
Additional byte 1 0xC2 (extension module error)
Additional byte 4: 0x08 Internal error
Additional byte 4: 0x09 Internal error
Additional byte 4: 0x0A Internal error
Additional byte 4: 0x1B Internal error
0x19 reserved
0x1A x
0x1B reserved
0x1C x
0x1D
SYSTEM CRASHED
Possible cause of the error:
There is strong EMC interference on MPA
0x1E x