Printed in Germany • Edition 04.18 • Nr. 271 958
Error overview
MPA 41xx PF
Errors from the extended functions (0x40 to 0x9F)
Error
ID
Internal
error
Error description
0x40 -
0x42
reserved
0x43 x
0x44 -
0x55
reserved
0x56 x
0x57 -
0x58
reserved
0x59
INTERFACE P2
Possible cause of the error:
The bus connection has been interrupted and the parameter P17 has been congured in a way
that a bus interruption triggers a safety shutdown followed by a fault lock, see P17: Temperature
controller operating mode
0x5A -
0x5F
reserved
0x60
CHANGE OF PARAMETER NOT RELEASED
A monitored parameter has been changed
Errors from the application (from 0xA0)
0xA0
x STATE DURATION TOOLING
Time in the parameterisation mode has elapsed
0xA1 reserved
0xA2
SAFETY CIRCUIT OPEN
Possible cause of the error:
The safety chain has been opened or is not closed
The wires of the safety chain are interrupted
0xA3 reserved
0xA4 x INTERNAL ERROR: FEEDBACK SIGNAL (V1)
0xA5 x INTERNAL ERROR: FEEDBACK SIGNAL (V2)