74 / 125
0006081263_200705
Display in parameterisation mode
Gas ring, pneumatic modulation
The changed address is not stored until you
advance the program or exit parameterisation
mode via timeout.
Specify post-ventilation time in seconds.
Permissible range: 0 - 240 s
The eBUS communication address. Possible
values are 03H, 13H, 33H, 73H, F3H, 1FH,
3FH, 7FH
Strike key (+) or (-) = slow variation occurs.
Hold down key (+) or (-) constantly = fast va-
riation occurs.
Each individual step occurs.