36
8.7 Optional Electrical Connections
A. Outdoor Temperature Sensor
To connect this accessory, see gure 8-5, terminals 4-5, and
instructions supplied with sensor.
B. Setting "Kt" Climate Curve
When external sensor is connected to boiler, the electronic
board adjusts the ow temperature calculated according to set
Kt coefcient.
Select required curve by pressing as indicated in
chart below for selecting the appropriate curve (00 to 90).
Flow temp Outside temp
NOTE:
Temperatures below -40 °F (-40 °C), maximum heating ow temperature set point no longer increases, curves shown on graph
become horizontal.
8 - ELECTRICAL CONNECTIONS
FIGURE 8-5 Outdoor Sensor Connections
FIGURE 8-6 Kt Climate Curves
90 Is Default.
240011947 REV B, [03/31/2018]