If Out1 is set for ##tP, #PUL, or ProP, then S1OL and S1OH (following) appear. If Out1 is set for
ONOF, then skip to S1rE.
S1OL Set Point Output Low Limit: Select 0 to 100% but not greater than S1OH. This item limits the
lowest output value. This is useful for adding a bias to the process when needed. Factory
set to 0 for output codes 1,2, and 3. Factory set to 20 for output code 5 (20% output equals
4 mA output).
S1OH Set Point 1 Output High Limit: Select 0 to 100% but not less than S1OL for output codes 1,
2, or 3. Select 0 to 102% but not less than S1OL for output code 5. This item allows setting
the maximum output limit. This is useful with processes that are overpowered. Adjustment to
102% allows setting current output to force a full on condition for output devices which do
not have bias adjustments. Factory set to 100 for all output codes.
If Out1 is set for ##tP, #PUL, or ProP, then skip to S1LP on next page.
S1rE Set Point 1 Reset. Select OnOF or Hold.
OnOF Control will automatically reset when process passes back through SP1d.
HoLd Manual Reset. Reset (acknowledge) by simultaneously pressing the INDEX &
DOWN ARROW keys for 5 seconds.
S1Pi Set Point 1 Power Interrupt. Select On or OFF.
On Alarm Power Interrupt is On. Control will automatically reset on power-up if no
alarm condition exists.
OFF Alarm Power Interrupt is OFF. Control will power-up in alarm condition regardless
of condition of process.
S1iH Set Point 1 Inhibit: Select On or OFF.
On Alarm Inhibit is On. Alarm action is suspended until the process value first enters
a non-alarm condition.
OFF Alarm Inhibit is OFF.
S1LP Set Point Lamp: Select O on or OoFF.
O on Lamp ON when Output is ON.
OoFF Lamp OFF when Output is ON.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dwyer Instruments LOVE CONTROLS 32A Series and is the answer not in the manual?

Dwyer Instruments LOVE CONTROLS 32A Series Specifications

General IconGeneral
BrandDwyer Instruments
ModelLOVE CONTROLS 32A Series
CategoryControl Unit
LanguageEnglish

Related product manuals