Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page 6
041736 N
Table 3.1
LKP Series 6 & 8 Channel Specifications, Continued
OUTPUTS
Current output:
1 A/5 kA, ±0.1% full scale
Voltage output, LKP-45, LKP-60 10mV per kA of bus current, ±0.1% full scale
Voltage output, LKP-80 1mV per kA of bus current, ±0.1% full scale
PHYSICAL
Overall Dimensions, in. (mm):
LKP Metering Unit (all)
48(1219)
H
x 36(914)
W
x 16(406)
D
LKP-45 Measuring Head
31 (772)
H
x 33(839)
W
x 6.7(170)
D
LKP-60 Measuring Head
36 (905)H x 40(1008)W x 11.8(300)D
LKP-80 Measuring Head
45 (1134)H x 48(1220)W x 11.8(300)D
Aperture Dimensions in. (mm):
LKP-45 Measuring Head
20.9 (530)
H
x 20.9(530)
W
LKP-60 Measuring Head
23.4 (595) H x 23.4(595)W
LKP-80 Measuring Head
30.5 (775) H x 30.5(775)W
Torque Head assembly bolts M8 tighten until snug
(head top half to bottom assembly) Never exceed 14 N.m (125 lb. in.)
NOTE
The Measuring Head window insulation rating is directly proportional to the clearance of the
Measuring Head to the bus. For instance, a bus in direct contact with the window insulation of
the Measuring Head will have an insulation rating of 6kV. A clearance of 1" increases the
window insulation rating to 12 kV. Thus, the greater the distance through the air between the
bus and the head, the greater the insulation rating will be.
Table 3.2
Typical Error At Zero Bus Current*
* See section 4.2 concerning magnetic effects of external buses.
Models
Max. Core Set
LKP-45
±6.75 amperes
LKP-60
±9 amperes
LKP-80
±12 amperes