Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page 8
041736 N
The Measuring Head should be a minimum
distance of 2a from another bus carrying
equal or less current. If the other bus
carries higher current, the distance should
be greater, e.g., 3a.
The Measuring Head should be located a
minimum distance of 2a from a 90° bend in
the bus.
If the Measuring Head is to be installed on a
U-section of the bus, the distance between
the parallel bus sections must be a minimum
of 4a, and the Measuring Head should be
centered between them.
If the Measuring Head is to be installed on a
T- section of the bus, it should be located a
minimum distance of 4a from the joining point.
Figure 4.1 General Guidelines for Locating Measuring Heads
4.3 MEASURING HEAD INSTALLATION
There are two connector fittings on the Measuring Head (one on each half). These fittings
are not to be used for lifting. Proper lifting is accomplished by using eyebolts in the holes
provided in the channel flanges or corners. Choker slings may be used around the
Measuring Head as long as strong lateral pressure on the edge of the window insulation is
avoided (see note below).