B3 ESS Unit User Manual
©Dyness reserves the copyright of this document.
9
If the master is the latest B3 battery with DIP switch:
5. If the battery communicates with the Schneider Conext Series, turn the master DIP
switch "#1" and "#3" to "ON".
Master Setting 4
6. When you setup the master DIP as setting 1~4,all the slaves keep the DIP 0000,no
need to change.
7. If the battery module is in communication with the ICC by 485 communication, turn
the master DIP switch "#1" and "#4" to "ON".
Master Setting 5
the DIP switch of slaves need to turn the “#4” to “ON” at the same time while the
master is setting 5.
Slave Setting 2
8. If the energy storage system has only one B3, it is the master itself, and still follow the
above steps.
Note: For more information of matching inverter brands, please subject to the latest
document
<The list of compatibility between Dyness ESS and Inverters >.
CAUTION
The DIP switch mode in case (7),1001 is only for ICC(a special communication device of
some no-communication inverter), it’s a special firmware in BMS,different from general
firmware,so if customers want to use ICC,please contact dyness to confirm.