CLASS 1000 METER
29 62-0388-01
Altitude 2000 Meters Maximum
Voltage Overload +25% Continuously: +100% For 20 Cycles
Current Sensor
Overload
100% For 1 Minute Without Damaging Meter
Pollution Degree Degree 2 In Accordance With IEC 664
Installation
(Overvoltage)
Category
Category 3
Measurement
Category
Category 3
Enclosure Material Indoor Housing Rating (Standard): UL Type 1
Outdoor Housing Rating (Optional): NEMA 4X
Display Readout KWh Accumulated, Instantaneous kW
Standard Ranges 3-wire 115/208 Vac; 25,50,100, 200
2 Phase 120/240 Vac; 25,50,100, 200, 400
IDR Interface Port Cable Specification: UL-listed/rated Telephone
Cord. 6 conductor.
Input/output Voltage: +5 VDC/18 VAC
Cable Connector: RJ-45 male IDC
Circuit Input Isolation: 5.3kVAC for one minute
Circuit output Isolation: 2.5kVAC
Isolated Pulse/Alarm
Outputs
Output Voltage Potential: 0 VDC to +5 VDC Logic Levels
Mating Plug Connector: Weidmuller PN: 152876
Signal Isolation Voltage: 5.3K VAC for 1 Minute
Recommended
In-line Fuse
Manufacturer: Littlefuse
Mfg. Part No.: KLDR.100
Rating: 100mA, Time-delay, 600VAC
Cartridge Fuse