EasyIO FG32 Installation Guide v2.0
12
Universal Input Connection
EasyIO FG and FG+ series has non-isolated universal inputs. The universal input supports three type of
analog signal i.e. resistance, voltage and current transmitter via hardware jumper and internal register
settings:
Universal Input
16 Channels (FG-32) , 12 Channels (FG-20)
Voltage
0 - 10V DC (+/-0.5V)
Current
0-20mA DC (+/- 0.5mA)
Resistance
0 - 500K (+/-10 Ohm), 0 - 10K (+/-5 Ohm), 0 - 1.5K (+/-1 Ohm)
Thermistor
10K, 10K Shunt, 1K Balco, 1K Platinum : All (+/-0.01 Deg-C)
UI as Digital Input
Voltage Free Contact
a) Resistance The working range of resistance is 500 Ohms 500K Ohms. The commonly used
Thermistor like 10K, 10K with Shunt, 1K Balco and 1K Platinum are all supported
b) Voltage Two selection of working range 0 5V and 0 10V. The minimum input
impedance of voltage input is 1 Mega Ohm.
c) Current Two selection of working ranges 0 20mA and 4 20mA. The current input
impedance is less than 25 Ohm.
d) Pulse Input All Universal Inputs are capable of receiving high speed pulse. Minimum on time
pulse is 25ms and minimum off time is 25ms. Max 20 Hz at 50% cycle.
Refer to image below.