EasyIO FG32 – Installation Guide v2.0
15
Universal Output Connection as Digital Output
Remarks: Universal Output as Digital Output
Only DC power source can be use. If AC power source it will damage the controller. Max DC power source
is 24VDC.
Max load for Universal Output as Digital Output is 200mA each channel.
Refer below table for software configurations of UO as DO. A Digital Output Block must be used.
EasyIO FG32 , FG32+
Physical Universal Output
Digital Output Block Channel
EasyIO FG20, FG20+
Physical Universal Output
Digital Output Block Channel