9. Introduction – 6000H(XL)/ 10000H(XL)
9.1 Product Specification and Performance
1) General Specification
Model 6000H 6000HXL 10000H 10000HXL
Power Rating 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 10KVA/7KW
Frequency (Hz) 50 50 50 50
Voltage (176-276)VAC (176-276)VAC (176-276)VAC (176-276)VAC
Input
Current 31A max. 31A max. 50A max 50A max.
Voltage 240VDC 240VDC 240VDC 240VDC
Battery
Current 24A max 24A max 40A max 40A max
Voltage 220VAC 220VAC 220VAC 220VAC
Output
Current 27A 27A 45A 45A
Dimension (WxDxH) mm 260x570x717 260x570x717 260x570x717 260x570x717
Weight (kg) 90 35 93 38
2) Electrical Performance
Input
Model Voltage Frequency Power Factor
6000H(XL)/10000 H(XL) Single-phase 46Hz-54Hz >0.98 (Full load)
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity
Current crest
ratio
±1%
0.7 lag
Synchronized
46-54Hz in
Line mode
(AC mode)
±0.1% of
normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)
105%-130% load
transfers to bypass
mode after 10 minutes
>130% load transfers
to bypass mode after 1
second and shutdown
the output after 1
minute
3:1
maximum
3) Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-40°C
<95% <1000m
0°C-40°
Note: if the UPS is installed or used in a place where the altitude is above than
1000m, the output power must be derated in use, please refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating Power 100% 95% 91% 86% 82% 78% 74% 70% 67%