Page 13
ENGLISH
Eaton 3S 450 550 700 850
UPS power 450 VA / 270 W 550 VA / 330 W 700 VA / 420 W 850 VA / 510 W
Input mains voltage 220 - 240 V~ ; Ph + N + PE
Input voltage range 184 - 264 V, adjustable to 160 - 284 V
Input frequency 50 / 60 Hz (46 - 65 Hz working range)
Input protection 10 A (thermal breaker)
Output Voltage for backup
outlets
220 V / 230 V / 240 V ~
Output Current for backup
outlets
2 A 2.4 A 3 A 3.7 A
Total output current for all
outlets
9 A maximum
Performance Classification VFD SY 333
Battery 12 V; 4.5 Ah 12 V; 5 Ah 12 V; 7 Ah 12 V; 9 Ah
Communication interface NA USB port (cable included)
USB Charge NA NA 2 USB ports 2 A maximum
Telephone surge protection
NA
NA
T3
Uoc = 6 kV; Up < 1.5 kV; In = 3 kA
Power surge protection
T3
Uoc = 6 kV; Up < 1.5 kV; In = 3 kA
Operating temperature 0 to 40 °C
Storage temperature -25 °C to +55 °C
Operating relative humidity Operating relative humidity 0 to 85 %
Operating elevation 0 to 3000 m
Compliances
IEC 62040-1; IEC 62040-2 C2*; IEC 62040-3; IEC 62040-4; IEC 61643-11
T3
Conformity
8. Specification and technical characteristics
Warranty 2 years
Weight 2.9 kg 3.2 kg 4 kg 4.3 kg
Dimensions 325 x 140 x 86 mm 335 x 170 x 86 mm
*Note:
The Eaton 3S is a IEC 62040-2 cat C2 UPS product. In a residential environment, this product may cause radio interference,
in which case the user may be required to take additional measures. Output cables should not exceed 10 m length.
CE / EAC / Ukr (DIN models)
CE / Cm (FR models)
CE / EAC / Cm / Ukr (IEC models)
614-09405-01 - 3S EMEA_EN