Eaton 5PX
Advanced User Guide
Copyright © 2021 EATON
All rights reserved.
614-40094-00
5PX1000IRT2UG2
5PX1500IRT2UG2
5PX2200IRT2UG2
5PX2200IRT3UG2
5PX3000IRT2UG2
5PX3000IRT3UG2
5PXEBM48RT2UG2
5PXEBM72RT2UG2
5PXEBM72RT3UG2

Questions and Answers

  • S
    sarahrichardsAug 5, 2025
    What to do if no battery LED is on and Eaton UPS beeps continuously?
    • R
      Rachael WatsonAug 5, 2025
      If your Eaton UPS is beeping continuously and the battery LED is off, it indicates that the batteries are disconnected. You should verify that all batteries are properly connected. If the problem continues after checking the connections, it may be necessary to contact your service representative.
  • Q
    qyorkAug 10, 2025
    What to do if the battery mode LED is on and Eaton 5PX3000IRT3UG2 beeps continuously?
    • J
      Joseph GreenAug 10, 2025
      If your Eaton UPS is beeping continuously and the battery mode LED is on, it means the battery test has failed due to bad or disconnected batteries. Verify that all batteries are properly connected. If the condition persists after checking the connections, contact your service representative.
  • S
    stewartdarleneAug 14, 2025
    Why is the battery mode LED on and Eaton UPS beeping every 10 seconds?
    • A
      Ashley WilliamsAug 14, 2025
      If the battery mode LED is on and the Eaton UPS beeps every 10 seconds, it indicates a utility failure, and the UPS is running on battery power. In this situation, prepare your equipment for shutdown, as the UPS is now providing backup power.
  • T
    Tiffany TerrellAug 18, 2025
    Why is the battery mode LED on and Eaton 5PX3000IRT3UG2 beeping every 3 seconds?
    • D
      dorissuttonAug 18, 2025
      If the battery mode LED is on and your Eaton UPS beeps every 3 seconds, it means the UPS is in battery mode and the battery is running low. The time to shutdown may vary depending on the UPS load and the number of Extended Battery Modules. The "Battery Low" warning may occur before the batteries reach 20% capacity.
  • J
    John ReynoldsAug 22, 2025
    What to do if the Power Overload LED is on for Eaton 5PX3000IRT3UG2?
    • A
      andrewhawkinsAug 22, 2025
      If the Power Overload LED is illuminated on your Eaton UPS, it means that the power requirements of the connected equipment exceed the UPS capacity. To resolve this, remove some equipment from the UPS. The UPS will continue to operate but may shut down if the load increases. The alarm will reset when the overload condition is no longer present.
  • P
    Paul HuffAug 27, 2025
    What to do if UPS over temperature LED is on and Eaton UPS beeps every 3 seconds?
    • S
      Sara GuzmanAug 27, 2025
      If the UPS Over temperature LED is On and Eaton UPS beeps every 3 seconds, it means the UPS internal temperature is too high or a fan has failed. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted and restart the UPS. If the condition continues to persist, contact your service representative.
  • H
    Henry JohnsonAug 31, 2025
    How to troubleshoot an Eaton 5PX3000IRT3UG2 UPS that does not start?
    • M
      mia07Aug 31, 2025
      If your Eaton UPS does not start, check the input and battery connections to ensure they are correctly connected.

Summary

Eaton 5 PX UPS Presentation and Overview

Standard Installation Options (Tower and Rack)

Describes tower and rack installation methods and provides dimensions.

Installation Guide for Eaton 5 PX UPS

Connecting Extended Battery Modules (EBM)

Step-by-step guide for connecting EBMs to the UPS.

Connecting the UPS to Power Source

Details how to connect the UPS to the AC power source and loads.

Interfaces and Communication Features

Control Panel and LCD Operations

Explains control panel, LCD display, and navigation functions.

User Settings and Configuration

Details adjustable user settings for language, alarms, and system parameters.

Operating the Eaton 5 PX UPS

Start-up and Normal Operation

Steps for starting the UPS and ensuring normal operation.

Shutting Down the UPS

Instructions on how to properly shut down the UPS.

UPS Maintenance and Care

When to Replace UPS Batteries

Information on battery lifespan and replacement notifications.

Replacing UPS Batteries

Detailed instructions and safety precautions for battery replacement.

Troubleshooting Common Issues

Typical Alarms and Faults Identification

How to check event and fault logs for UPS issues.

Technical Specifications and Characteristics

Eaton 5PX3000IRT3UG2 Specifications

General IconGeneral
Form FactorTower
Power Rating3000 VA / 2700 W
Output Voltage200 / 208 / 220 / 230 / 240 V
Output Frequency50/60 Hz
Number of Outlets8
Operating Humidity0% to 95% (non-condensing)
Input Voltage200-240 VAC
Input ConnectionIEC C20
Battery TypeSealed Lead-Acid (SLA)
EfficiencyUp to 95%
CommunicationUSB, RS232
Typical Recharge Time3 hours
Operating Temperature0 to 40°C (32 to 104°F)
TopologyDouble Conversion
Network ManagementOptional network card (Web/SNMP)
Communication Ports1 x USB, 1 x RS232