1.
2.
3.
Installation of the communication cards
It is not necessary to shutdownthe UPS before
installinga communication card.
Remove the slot cover (9)secured by screws.
Insert the communicationcard in the slot.
Secure the card cover withthe two screws to
connect the comm card to the ground.
4.6 UPS remote control functions
Connectivity cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with differenttypes of
devices. The5PXmodels have one available communication bay for the following connectivity cards:
Gigabit Network card(Network-M2) : provides a Gigabit Ethernet connection and enables secure UPS monitoring
over HTTPS web browser interface, SNMP v1/v3 protocol and email alarms. In addition, up to 3 Environmental
Monitoring Probes can be attached to obtain humidity, temperature, smoke alarm, and security information.
Industrial Gateway card(INDGW-M2) :Provides Modbus RTU and Modbus TCP communication support in addition
to the same secure UPS monitoring, management and sensor capability as the Gigabit Network card.
Relay-MS card: provides isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPS
alarm/OK, or on Bypass.
INDRELAY-MS : The Industrial relay Card-MS (INDRELAY-MS) provides a simple way to remotely input UPS information
to an alarm system, PLC or a computer system via dry contacts. It offers five isolated dry contact outputs and one
isolated dry contact input.