EasyManua.ls Logo

Eaton 9SX 20KPM Series - UPS Setting

Eaton 9SX 20KPM Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
7.3.3 UPS operation control
Select Control from the Menu page to enter the Control page. This page requires
the user password by default. If the password is entered incorrectly for 3
consecutive times within 5 minutes, the LCD will switch back to the main page.
Following this, the Control and Setting will be locked for 5 minutes and will not
be able to be operated during this timePassword protection can be disabled
under: Setting Password:
In a Paralleled system, there are 6 kinds of control operations available as shown
in the figure above. In a Single UPS system, only 4 kinds of control operations
are available.
Control function
Description
Battery Test
Start a manual battery test
Manual Bypass
Forces the UPS to enter or exit bypass mode manually,
if conditions permit.
Single UPS
Shutdown
Manually shuts down this UPS
Reset Alarm
Clears all alarms during fault mode.
Control function
Description
Restore Factory
Settings
Restore all settings to the default factory settings.
This is only permissable in bypass mode.
Battery Test (Parallel)
Start a manual battery test for all UPS in a paralleled
system.

Related product manuals