7
Installation manual 3A3718 Rev E
Effective February 2019
CCP2-H4X-_ pistol handles for 12 mm shafts
Eaton.com/bussmannseries
Right side clockwise handle
operation and installation
The following applies to all clockwise
operating handles.
Procedures for clockwise handle
catalog numbers:
•
CCP2-H4X-B3 (short)
•
CCP2-H4X-R3 (short)
•
CCP2-H4X-B4 (long)
•
CCP2-H4X-R4 (long)
For installation with switch catalog
numbers:
•
CCP2-(poles)-200CF
•
CCD2-3-200
•
CCP2-(poles)-400CF
•
CCD2-3-400
And requires installation of:
•
The side rotary mechanism:
• CCP2-SM mounted on the switch’s
right side
•
Either shaft catalog numbers:
• CCP2-SH2-225
• CCP2-SH2-425
OFF
ON
OFF
Switch operating modes
NOTE: Side installation
(handle mounted on the
enclosure’s side and not
the door) does NOT provide
for an interlock means to
prevent opening the door
while the switch is in either
the ON or OFF position.
If preventing access to
the enclosure’s interior is
desired or required by the
application, use a locking
door latch or install a suitable
hasp to accept a lock.
Handle lock ON operation
Note: NOT to be utilized when switch is applied as a means for emergency stop.
ON
OFF
X
X
ON
ON
ON
OFF
OFF
OFF
X
3 N•m (27 lb-in)
Break out this
portion of
the bezel
2.5 mm Allen wrench
To enable the handle’s lock ON feature:
•
Use a 2.5 mm Allen wrench to loosen the setscrew and remove the handle from the handle
base as shown.
•
Using needle nose pliers, break off the retaining stop on the switch handle bezel as shown.
•