TABLE 5-3. Function Codes (continued)
Func.
Code 
Level 1 
Main Menu
Level 2 
Sub-Menu
Level 3  
Parameter
Security Level Factory 
Setting
Key Entry Limit
Read Edit Reset Low High
60 Features Communications 060 Com Port #1
Protocol 
DNP
0 2 NA DNP NA NA
•  This function defines which resident protocol of the control will be used on Com1/Com3. 
•  Options include:
    • DNP      • 2179
•  See the Control Features: Digital SCADA section of this manual.
61 Features Communications 061 Com Port #1 
Speed 
9600
0 2 NA 9600 NA NA
•  The control microprocessor has two communications channels, each with selectable baud rates. 
•  Options for Com1/Com3 include:
    • 300  • 600     • 1200     • 2400 
    • 4800   • 9600     • 19200    • 38400
62 Features Communications 062 Com Port #1 
Sync Time 
0 mSec
0 2 NA 0 0 65535
•  This defines the period of time, for Com1/Com3, the received data line must idle to assume the start of a request 
message. 
•  See the Control Features: Digital SCADA section of this manual.
63 Features Communications 063 Com Port #1 
DNP Master Adrs 
1234
0 2 NA 1234 0 65535
•  The control will send unsolicited responses to this master address for Com1/Com3.
64 Features Communications 064 Com Port #1 
DNP Remote Adrs1
1
0 2 NA 1 0 65535
•  This is the primary DNP remote address used by user.
•  The DNP Remote Address 1 for Com1/Com3 is entered at FC 64.
64
Features Communications 064 Com Port #1 
DNP Remote Adrs2
65519
0 2 NA 65519 0 65535
•  This is the DNP remote address available for remote configuration. For more information, contact your Eaton 
representative.
•  The DNP Remote Address 2 for Com1/Com3 is entered at FC 64.
53