Transfer Dimensions & Conduit Opening Wt.
Switch A B C D
Rating in (cm) in (cm) in (cm) in (cm) lb (kg)
3 Pole
Fixed 28.00 (71.1) 50.00(127.0) 23.50 (59.7) 22.00 (55.9) 1300 (590)
800-1200
➀
4 Pole
Fixed 34.00 (86.4) 50.00 (127.0) 29.50 (74.9) 22.00 (55.9) 1400 (635)
800-1200
➀
3 Pole
Fixed 48.00 (121.9) 60.00 (152.4) 43.25 (109.9) 22.00 (55.9) 1900 (862)
2500-4000A
4 Pole
Fixed 48.00 (121.9) 60.00 (152.4) 43.25 (109.9) 22.00 (55.9) 2100 (953)
2500-4000A
Side View
800-2000 amperes, 3 or 4 Poles
800-1200 only if Option 17C is selected
Side View
➀
800-1200A supplied with Option 17C
2500-4000 amperes, 3 Poles
2500-3000 amperes, 4 Poles
Front View
Front View
Dimensions are in inches
(centimeters).
Top View
AUTOMATIC, NON-AUTOMATIC AND
MANUAL TRANSFER SWITCHES
Enclosures meet all current applicable NEMA and UL standards for con-
duit entry, cable bending, gutter space and shielding of live components.
NEMA 1 Enclosures
NEMA 1 Transfer Switches are supplied with a front door only.
They can be mounted in a corner or against a wall. Access to
cable space can be via either side, bottom, top, or the rear.
NEMA 3R Enclosures
Additional 2” (5.1cm) clearance on each side of enclosure for
hooded vent patterns.
Requires appropriate rear-end clearance based on 26-34”
(66-86cm) door (800-2000A) or 31” (61cm) door (2500-
4000A).
NEMA 3R Transfer Switches are supplied with front & rear doors.
They can be mounted against a wall (allowing for hooded vent
pattern clearance), but not in a corner. Access to cable space is
via rear only.
NOTE: When open switch is mounted in customer enclosure, a vent pat-
tern similar to that used on a Culter-Hammer enclosure must be utilized.
Transfer Dimensions
Switch F G H I
Rating in (cm) in (cm) in (cm) in (cm)
2000A Fixed 71.00 (180.3) 54.50 (138.4) 38.00 (96.5) 29.54 (75.0)
3000A Fixed 67.00 (170.2) 47.00 (119.4) 27.00 (68.6) 36.03 (91.5)
4000A Fixed 69.12 (175.6) 45.12 (114.6) 21.12 (53.6) 33.16 (84.2)