I.B. 17555C
Effective November 1999
Page 18
2-3 DT3000 AND DT3030 SPECIFICATIONS AND TEST SUMMARY (CONTINUED)
ENVIRONMENT:
• Environment: Indoor Use Only, Pollution
Degree II, Altitude 2,500m,
Installation Category II
• Mounting Location: Device should be positioned
near the main disconnect
• Operating temperature: -30 to +55 Degrees Celsius
• Operating Humidity: 0 to 95% Relative Humidity
[Non-Condensing]
• Storage Temperature: -40 to +70 Degrees Celsius
ADDITIONAL TESTS:
• Dielectric Strength: Current Inputs: 3,000Vac for
1 minute Phase to Phase
• Seismic Test: Meets requirements for UBC and
California Building Code Zone 4
ZPA = 3.5
AUXILIARY RELAYS:
(Protection Off Alarm and Trip Alarm)
• Make/Break: 5A @ 120/240Vac & 30Vdc
• Continuous: 5A @ 120/240Vac
5A @ 30Vdc
ZONE SELECTIVE INTERLOCKS:
• Phase: Inverse Time Overcurrent and
Short Delay
• Ground: Inverse Time Overcurrent and
Short Delay
COMMUNICATIONS:
• PowerNet Compatible / Built-in INCOM
• Data Rate is 1200 or 9600 Baud
• Set INCOM address from front panel
Notes: 1. For Ground Pickup < 0.2pu; Time Tolerance ± 15%.