I.B. 17555C
Effective November 1999
Page 18
2-3 DT3000 AND DT3030 SPECIFICATIONS AND TEST SUMMARY (CONTINUED)
ENVIRONMENT:
Environment: Indoor Use Only, Pollution
Degree II, Altitude 2,500m,
Installation Category II
Mounting Location: Device should be positioned
near the main disconnect
Operating temperature: -30 to +55 Degrees Celsius
Operating Humidity: 0 to 95% Relative Humidity
[Non-Condensing]
Storage Temperature: -40 to +70 Degrees Celsius
ADDITIONAL TESTS:
Dielectric Strength: Current Inputs: 3,000Vac for
1 minute Phase to Phase
Seismic Test: Meets requirements for UBC and
California Building Code Zone 4
ZPA = 3.5
AUXILIARY RELAYS:
(Protection Off Alarm and Trip Alarm)
Make/Break: 5A @ 120/240Vac & 30Vdc
Continuous: 5A @ 120/240Vac
5A @ 30Vdc
ZONE SELECTIVE INTERLOCKS:
Phase: Inverse Time Overcurrent and
Short Delay
Ground: Inverse Time Overcurrent and
Short Delay
COMMUNICATIONS:
PowerNet Compatible / Built-in INCOM
Data Rate is 1200 or 9600 Baud
Set INCOM address from front panel
Notes: 1. For Ground Pickup < 0.2pu; Time Tolerance ± 15%.