EasyManua.ls Logo

Eaton DT3000 - Page 78

Eaton DT3000
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.B. 17555C
Effective November 1999
Page B2
Fig. B-1 Digitrip 3000 with DSPS
NOTE: The following material replaces section 2-3, pages 16 & 17.
TABLE B-2 DT3010 AND DT3020 SPECIFICATION AND TEST SUMMARY
COMPLIANCE TESTING:
Certifications:
UL Recognized, File # E154862
UL 1053 (1994)
ANSI C37.90 (1989)
EN 55011 (1991)
Emission Tests:
EN 55011 (1991) – Group 1 Class A
FCC 47 CFR Chapter 1 - Part 15 Subpart b Class A
Immunity Tests:
ANSI C37.90.1 (1989) - Surge Withstand Capability
EN 61000-4-2 (1995) - ESD Rating of 8kV
IEC 255-22-2 (1989) - ESD Rating of 8kV
EN 61000-4-3 (1997) – Radiated EM Field at 10V/m
IEC 255-22-3 (1989) - Radiated EM Field at 10V/m
IEC 801-3 (1984) - Radiated EM Field at 10V/m
EN 61000-4-4 (1995) – Fast Transient Burst at 2kV
IEC 255-22-4 (1992) - Fast Transient Burst at 2kV
EN 61000-4-6 (1996) - Conducted RF at 10V/m
PHASE AND GROUND TIME-CURRENT CURVES:
Thermal It [Moderately Inverse]
I2t [Very Inverse]
I4t [Extremely Inverse]
Flat [Definite Time]
ANSI: Moderately Inverse
(Per ANSI C37.112, 1996) Very Inverse
Extremely Inverse
IEC: IEC-A [Moderately Inverse]
(Per IEC 255-3, 1989 IEC-B [Very Inverse]
IEC-C [Extremely Inverse]
IEC-D [Definite Time]
CONTROL POWER:
Input Voltage: Nominal
Operating Range
DT3010: 100 - 120Vac 70 – 132Vac, (50/60Hz)
DT3020: 200 - 240Vac 140 - 264Vac, (50/60Hz)
Power Consumption: 15VA maximum

Table of Contents