2. Installation
--6--
4) Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.
Note: you must make sure that the input and output wires and the input and output
terminals are connected tightly
5) The protective earth ground wire refers to the wire connection between the
equipment which consumes electric equipment and the ground wire. The wire
diameter of protective earth ground wire should be at least as above mentioned
for each model and green wire or green wire with yellow ribbon wire is used.
6) After having completed the installation, make sure the wiring is correct.
7) If earth leakage protection is required, please install the earth leakage protection
device in output power distribution panel of the UPS.
8) To connect the load to the UPS, please turn off all the loads first, then perform the
connection and finally turn on the loads one by one.
9) Whether or not the UPS is connected to the utility power, the output of the UPS
may be live. The parts inside the unit may still have hazardous voltage after
turning off the UPS. To fully de-energise the UPS, power off the UPS, and then
disconnect the utility power supply.
10) It is advisable to charge the battery for 8 hours before using it, so as to ensure
adequate. After connection, turn the bypass breaker in the ON position, the UPS
will charge the batteries automatically.
11) If it connect to the inductance load such as a monitor or a laser printer to the UPS,
the start-up power should be used for calculating the capacity of the UPS, as its
start-up power consumption is too big.