2. Programming Concepts
MN05003003E For more information visit: www.eaton.com
2-23
SM
Function
ELC
-PB
ELCB
-PB
ELC
-PC
-PA
-PH
ELCM
-PH
-PA
ELC
-PV
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Type Latched
Factory
setting
M1091
Matrix finding bit flag. When find it, it will
stop comparing and M1091=1.
- Y Y Y OFF OFF - R NO OFF
M1092
Matrix pointer error flag. When pointer Pr
exceeds this range, M1092=1.
- Y Y Y OFF OFF - R NO OFF
M1093
Matrix pointer increase flag. It will add 1
to present pointer.
- Y Y Y OFF OFF - R/W NO OFF
M1094
Matrix pointer clear flag. It will clear
present pointer to 0.
- Y Y Y OFF OFF - R/W NO OFF
M1095
Carry flag for matrix rotate/shift output
- Y Y Y OFF OFF - R NO OFF
M1096
Complement flag for matrix shift input
- Y Y Y OFF OFF - R/W NO OFF
M1097
Direction flag for matrix rotate/shift
- Y Y Y OFF OFF - R/W NO OFF
M1098
Matrix count bit 0 or 1 flag
- Y Y Y OFF OFF - R/W NO OFF
M1099
It is ON when matrix count result 0
- Y Y Y OFF OFF - R/W NO OFF
M1100
SPD instruction sampling once
- - - Y OFF - - R/W NO OFF
M1101
Start file register or not
- Y - Y - - - R/W Yes OFF
ELC-PH only : Y10 end flag of pulse
output
- Y - -
M1102
Y2 pulse or CH1 (Y2, Y3) pulse output
execution completed
- - Y -
OFF - - R/W NO OFF
ELC-PH only : Y11 end flag of pulse
output
- Y - -
M1103
Y3 pulse output completed
- - Y -
OFF - - R/W NO OFF
M1104
Y2 pulse or CH1 (Y2, Y3) pulse output
pause (immediate)
- - Y - OFF OFF - R/W NO OFF
M1105
Y3 pulse output pause (immediate)
- - Y - OFF OFF - R/W NO OFF
M1108
Y0 pulse or CH0 (Y0, Y1) pulse output
pause (ramp down)
- - Y - OFF OFF - R/W NO OFF
M1109
Y1 pulse output pause (ramp down)
- - Y - OFF OFF - R/W NO OFF
M1110
Y2 pulse or CH1 (Y2, Y3) pulse output
pause (ramp down)
- - Y - OFF OFF - R/W NO OFF
M1111
Y3 pulse output pause (ramp down)
- - Y - OFF OFF - R/W NO OFF
M1112
Switching time resolution of Y0 for PWM
instruction (ON: 100us; OFF: 1ms)
- - Y - OFF OFF - R/W NO OFF
M1113
Switching time resolution of Y2 for PWM
instruction (ON: 100us; OFF: 1ms)
- - Y - OFF OFF - R/W NO OFF
M1115
Start switch for accel/decel pulse output
(not available in ELC-PH_VERSION 1.4
and above)
Y Y - - OFF OFF OFF R/W NO OFF
M1116
Acceleration flag (not available in ELC-
PH _VERSION 1.4 and above)
Y Y - - OFF OFF OFF R/W NO OFF
M1117
Target attained frequency flag (not
available in ELC-PH _VERSION 1.4 and
above)
Y Y - - OFF OFF OFF R/W NO OFF