4. Access to Maintenance and Personalization Data
Insert the Solution-Pac CD-ROM in the drive.
w On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
w Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal Solution-Pac
software).
Main-output personalization
Function Factory setting Other available settings
Output voltage on battery power 120 Volts AC 100/120/127 Volts AC
Overload alarm threshold 105% 30/50/70%
Voltage-threshold personalization
Function Factory setting Other available settings
High threshold for transfer to
battery
151 Volts AC ±3% 141 to 153 Volts AC
Low threshold for transfer to battery 89 Volts AC ±3% 80 to 94 Volts AC
Fader activation threshold 132 Volts AC ±3% 127 to 138 Volts AC
Booster activation threshold 102 Volts AC ±3% 92 to 108 Volts AC
Maximum input-voltage range Disabled Enabled
UPS-sensitivity personalization
Function Factory setting Other available settings
UPS-sensitivity level Normal High or low
86-81700-00EN A02 - Page 19