Engine Board Terminal Blocks
Field Connections
Diesel Plus Engine Controller
Technical Data TD081020EN
E ective April 2015
Inputs
Outputs
7HFKQLFDO'DWDDQG6SHFLᚏFDWLRQV
/LQH7HUPLQDOV,QFRPLQJ&DEOHV
Recommended Wire Size Terminal Number Distance
I/O Board
Stranded # 14 (1.63mm)
Stranded # 14 (1.63mm)
11, 34-39, 60-95
Option Board Terminals
N. A.
N. A.
Engine Board
Stranded # 14 (1.63mm)
1-5, 9, 10, 12, 301, 302, 303, 304, 310, 311, 312
L, N, G
N. A.
Battery Wire
Stranded # 10 (2.59mm)
Stranded # 8 (3.26mm)
6, 8, 11
6, 8, 11
0 feet to 25 feet (7.62m)
25 feet to 50 feet (7.62-15.24m)
Field Connections
100-240VAC POWER
BATTERY #2 CRANK
FUEL INJECTOR FAIL
ECM IN ALTERNATE
BATTERIES (-)
BATTERIES (-)
ECM WARNING
HIGH RAW WATER TEMP
ECM FAILURE
LOW ENGINE TEMPERATURE
LOW RAW WATER FLOW
BATTERY #1 INPUT(+)
FUEL & WATER SOLENOID VALVE
OIL PRESSURE SW.
ENGINE RUN SW.
OVERSPEED SW.
ENGINE WATER TEMP. SW.
FUEL SOLENOID
BATTERY #2 INPUT(+)
BATTERY #1 CRANK
INPUT #1
LOW FUEL
INTERLOCK ON
DELUGE VALVE
INPUT #4
INPUT #3
INPUT #2
INPUT #6
INPUT #5
INPUT #7
INPUT #8
REMOTE START
INPUT #9
FUEL SPILL
PUMP START
LOW SUCTION
ENGINE RUN
FUTURE #1
FUTURE #1
NOTE: OUTPUT STATES SHOWN ARE WHEN CONTROLLER IS POWERED AND SET IN OFF MODE
(ENERGIZED)
FUTURE #2
FUTURE #2
ENGINE RUN
LOW FUEL
LOW FUEL
AUTO MODE
AUTO MODE
COMMON ALARM
COMMON ALARM
(ENERGIZED)