Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05 5
CChhaapptteerr 22 SSyysstteemm OOppttiioonnss OOvveerrvviieeww
22..11 FFXX RReemmoottee CCoonnttrrooll DDiissppllaayy ((RRCCDD))
The Remote Control Display (RCD) is included with all Eaton Ferrups FX UPS models providing hand held operation enabling the
end user to communicate and interpret UPS operating modes, alarms and events. The RCD is connected to the UPS via a
standard 28 inch ethernet cable. The ethernet cable can be extended for RCD use up to 150 feet from the UPS and can be
mounted to a metal surface via the magnetic strip located on the back of the RCD.
Figure 2. Eaton Ferrups FX Remote Control Display
22..22 BBaatttteerryy CCaabbiinneettss
If you need extended runtime, contact Eaton or your local distributor for information on adding additional Eaton FX FERRUPS
battery options.
There are two types of external battery cabinets that can be used with the Eaton Ferrups FX UPS. The N
cabinet and the P cabinet. External battery cabinets offer several options to extend battery runtime ( See
Table 1 ) . The Eaton Ferrups FX UPS can have a maximum of four EBM units connected.
Table 1. External Battery Cabinet Options
Eaton Ferrups FX External Battery
Runtime Opitons
Battery Cabinet Type Type and Number of Batteries
FXEBM01 N
Qty 8 (12 Volt) PWHR12280W4FR
(48VDC)
FXEBM03 P
Qty 12 (12 Volt) PWHR12280W4FR
(48VDC)
FXEBM04 P
Qty 12 (12 Volt) PWHR12330W4FR
(48VDC)
FXEBM05 P
Qty 12 (12 Volt) PWHR12620W4FR
(48VDC)
FXEBM06 P
Qty 12 (12 Volt) SWU585–12FR (48VDC)