38 Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range Description
7 “07 V Batt 48.1 V” Service 0.0 175.0
Measured average DC volts of the UPS
battery. Programming changes an internal
setting to calibrate reading.
8
“08 Freq 60.00 Hz”
No Change
Allowed
47.00 63.00
Line input frequency when line is OK. Line
output frequency otherwise. Display
parameter only, unprogrammable.
9 “09 RunTime 12 m”
No Change
Allowed
0 9999
Approximate runtime presently available to
the load during inverter operation. Display
parameter only, unprogrammable.
10 “10 Date 01/01/20” User 01/01/00 12/
31/99
Today’s date in Mo/Dy/Yr format. Date is
set to last known date whenever UPS is
turned on. UPS internally sets years
between 2000–2099.
11
“11 Amb Temp 23 C” No Change
Allowed
–63 193
Temperature of air around logic board.
12 Reserved
13 Reserved
14
14 Xfmr Temp 28 C
No Change
Allowed
–63 193
Transformer temperature. The FerrUPS will
alarm if this value is too high. This
parameter is only for models that monitor
transformer temperature; for other models,
this parameter will always show -63° C.
15
“15 Unit ID “Network
#1 UPS”
No Change
Allowed
0 20 chars
Provides user configurable identification
string of the UPS. Usually used in network
configurations.
16 “16 FullLoad% 75”
No Change
Allowed
0 150
FullLoad% = (VAOut/VALimit) * 100. Display
parameter only, unprogrammable.
17 “17 Watts 374”
No Change
Allowed
0 15000
Watts being used by load. = Instantaneous
dot product of ACVoltsOut x ACAmpsOut.
(average power)
18
“18 PF 0.73 Lead” or
“18 PF 0.82 Lag” or
“18 PF 1.00 —”
No Change
Allowed
0.00 1.00
Power factor of user load. PF types: Lead,
Lag, Distortion or (Indeterminate)
depending on load type. PF magnitude =
Watts / VA Out. The unit should always
display 1.00 for loads < 25%
19 “19 VALimit 2200 VA”
No Change
Allowed
350 18000
Max allowable load in VA. Limit changes
depending on load type. For “Lead” or
“Dist” types the unit is prorated as: VALimit
= RatedWatts/PF.
20
20 ActiveAlm "Batt
Disconnected"
No Change
Allowed
N/A
It will scroll all Active alarms, each for 3
seconds. User can toggle scrolling by
pressing '0'. When scrolling is stopped,
pressing '1' will move to next event (older).
UPS Parameters