Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05 39
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range Description
List will wrap to newest event from oldest
event.
21–23 Reserved
24
"24 Logs #69 CLR"
"RCD Attached" "2020/
03/06 11:35:44"
No Change
Allowed
N/A
Log of events and alarms. Display event
number and CLR (cleared) or SET (set).
Following lines have text description and
date/time of event. Scrolls from most recent
to oldest event every 3 seconds. User can
toggle scrolling by pressing '0'. When
scrolling is stopped, pressing '1' will move
to next event (older). List will wrap to
newest event from oldest event.
25 Reserved
26
"26 BT Results"
“Okay”
N/A
SERVICE REQUIRED/Failed Discharge/Okay
27 “27 Crest 1.41”
No Change
Allowed
0.00 5.00
Crest Factor = (peak AC amps out) / (RMS
AC amps out). CF = 1.41 if ACAO waveform
is a sine wave or if load < 25%. Display
parameter only, unprogrammable.
28–38 Reserved
39
39 CTO
"FX310000AAA1"
No Change
Allowed
0 20
characters
CTO describes UPS configuration. When
programmed, also changes Rated VA, Rated
Watts, Nominal Voltage In, Nominal Voltage
Out, etc.
40
40 Serial Number
"FE10K25000"
No Change
Allowed
0 20
characters
Provides factory configurable serial number
identification of the UPS.
41
41 Model Number
"FX3100"
No Change
Allowed
FX1150 - FX18K0 Text of Model number.
42
42 NomFrq 1)60 Hz
No Change
Allowed
1) 60Hz
Nominal frequency of line input/output
voltages. 60Hz supported, this parameter is
non-programmable.
43 43 NomVIn 120.0 V
No Change
Allowed
60.0 500.0
Nominal AC line cord input voltage to the
UPS.
44 44 NomVOut 120.0 V
No Change
Allowed
60.0 500.0
Nominal AC line output to user load.
45 45 RatedVA 3100 VA
No Change
Allowed
100 30000
Maximum Rated VA UPS may deliver to
user load without alarming under any
circumstances. .
46 46 RatedW 2200 W
No Change
Allowed
100 30000
Maximum rated Watts UPS may deliver to
user load.
47–57 Reserved
58
58 XferDly 5 s
Service 1 600
Minimum number of seconds the UPS will
run on inverter before transferring back to
AC line operation. Actual time on inverter
UPS Parameters