70 Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 29. Typical Alarm Conditions (Continued)
91
UPS STATE
CHANGE
Status Reporting a state
change from one mode
to another
Supporting Load Nothing.
92 AMBIENT
OVERTEMPERA-
TURE TRIP
A Ambient temperature
too high above max
specification
Off Check if Fan(s) are not
running. Check if room
temperature is > 40C. If not,
call Eaton Service.
93
CHARGER
OVERTEMPERA-
TURE
A Charger reporting over
temperature
On but charger is off Call Eaton Service
94
CHARGER
OVERTEMPERA-
TURE TRIP
A Charger reporting over
temperature and turned
off
On but charger is off Call Eaton Service
95
SCR
OVERTEMPERA-
TURE
A SCR Heatsink on AC
Board reporting over
temperature
On Call Eaton Service
96
SCR
OVERTEMPERA-
TURE TRIP
A SCR Heatsink on AC
Board reporting over
temperature and UPS
transferred to Battery
On Call Eaton Service
97 DVR
OVERTEMPERA-
TURE
A DVR reporting over
temperature
On Call Eaton Service
98
DVR
OVERTEMPERA-
TURE TRIP
A DVR reporting over
temperature
On Call Eaton Service
99 XFMR
OVERTEMPERA-
TURE
A Ferro Transformer
reporting over
temperature and UPS
turned off
On Call Eaton Service
100 XFMR
OVERTEMPERA-
TURE TRIP
A Ferro Transformer
reporting over
temperature and UPS
turned off
On Call Eaton Service
Alarm Conditions