EasyManua.ls Logo

Eaton Freedom 2100 - Incoming Line Connection Procedures; Incoming Line Overcurrent Protection and Disconnects

Eaton Freedom 2100
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- Page 13 -
I.B. 8926-1
OVERCURRENT PROTECTION
All ungrounded conductors in a motor control center
(MCC) installation require some form of overcurrent pro-
tection in order to comply with Section 240-20 of the NEC.
Such overcurrent protection for the incoming lines to the
MCC is in the form of fuses or a circuit breaker located
at the transformer secondary that supplies the MCC. The
conductors from the transformer secondary constitute
the feeder to the MCC, and the “l 0-foot rule” and the
“25-foot rule” of NEC 240-21 apply. These latter excep-
tions to the general rule allow the disconnect means and
overcurrent protection to be located in the MCC, pro-
vided the feeder taps from the transformer are sufficiently
short and other requirements are met.
MAIN DISCONNECTS
A circuit breaker or a circuit interrupter combined with
fuses controlling the power to the entire MCC may pro-
vide the overcurrent protection required as described
above or may be a supplementary disconnect (isolation)
means. See Figures 17, 18 and 19.
When the MCC has a main disconnect, bring the incom-
ing lines (the feeders) to the line terminals of the circuit
breaker or circuit interrupter. The load side of the
PART 5
INCOMING LINE CONNECTIONS
Fig. 17 Main Disconnect with Stab Load Connections
Fig. 18 Main Circuit Breaker with Reverse Feed

Related product manuals