Installation i-on40
Page 16
Figure
29
Fully Supervised Loop Zone Wiring
Figure
30
Example: Wiring Two Door Contacts to
One FSL Zone.
Figure 31 shows an example of wiring a
trouble/masking output using the “3-resistor
method”. Note that you must use 2k2 and 4k7
resistors as shown. Other values will not work
(See System Options Masking in the i-on
Engineering Guide).
Figure
31
Example: Wiring a Trouble/Masking
Zone, 3 Resistor Method.
Connecting Wired Zones on KEY-KPZ01 only)
The KEY-KPZ01 provides terminals for up to two
zones. You must enable the zones from the
Installer Menu Detectors/Devices Wired Keypads
Edit Keypad (keypad number) Zones.
Once the zones are enabled they occupy the zone
numbers at the top of the numbering range,
depending on the address of the keypad.
Keypad zone
Panel
zone
FSL
Panel Zone
CCL
Keypad 1 Zone 1
39
39 Alarm
Keypad 1 Zone 2
40
39 Tamper
Keypad 2 Zone 1
37
37 Alarm
Keypad 2 Zone 2
38
37 Tamper
Keypad 3 Zone 1
35
35 Alarm
Keypad 3 Zone 2
36
35 Tamper
Keypad 4 Zone 1
33
33 Alarm
Keypad 4 Zone 2
34
33 Tamper
To select the wiring type for the keypad zones use
Installer Menu - System Options - Wired Zone Type
All Zones. Alternatively, to select the wiring type for
an individual keypad, use Installer Menu
Detectors/Devices Wired Keypads Edit Keypad
(keypad number) Wired Zone Type.
Figure 32shows the wiring connections for FSL
zones on a KEY-KPZ01. Note that the resistance
values shows are examples.
Figure
32
Wiring FSL Zones on KEY-KPZ01
Figure 33 shows the wiring connections for
Closed Circuit Loop connections to the zones on a
KEY-KPZ01,
Figure
33
KEY-KPZ01 CCL Zone Wiring
Zone 1
Zone 2
2K2 EOL
4K7
Alarm contacts
Tamper contacts
2K2 EOL
4K7
Alarm contacts
Tamper contacts
Zone 1
2K2 EOL
4K7
Alarm contacts Alarm contacts
Tamper contacts Tamper contacts
Max 10 devices per circuit (not recommended)
100 Ohms
2K2 EOL
Spare
4K7
Black
Red
Blue
To zone
contacts
Yellow
KEY-KPZ01
Zone 0
Zone 1
2K2 EOL
4K7
Alarm contacts
Tamper contacts
2K2 EOL
4K7
Alarm contacts
Tamper contacts
100 Ohms
Tamper Zone 1
Alarm Zone 1
KEY-KPZ01