Unit description
11
11/01 AWB2300-1433GB
Thermistor protection
Full motor protection can be achieved by connecting up to 
six DIN 44081 and DIN 44082 PTC temperature probes with 
a resistance of R
K 
F 250 O to the terminals T1-T2.
NAT = RTT = Rated Threshold Temperature
Figure 4 : Characteristics curve of temperature monitoring with 
thermistor
a Tripping
b Reset
c Three temperature probes
d Six temperature probes
The ZEV trips at R = 3200 Og15 % and resets at 
R = 1500 O +10 %. The contacts 9596 and 9798 change 
over when the unit is tripped by the signal at the thermistor 
input. The thermistor tripping circuit can also be assigned to 
switch over one of the contacts 05-06 or 07-08, in order to 
provide a distinguished tripping indication (a fig. 7, 
Page 18).
R
 
[O]
5000
10000
2000
3680
1500
1000
900
800
700
600
500
a
c
d
b
NAT
 -10
-20
+10
+5
+20 +30
 -30
K