IM02602002E
Page 3-2
www.eaton.com
MP-3000

Accuracy: Free running ± 1 min./mo.
@ 25°C (77°F). Automati-
cally updated by PowerNet
host.
(Section 10 contains more protocols.)
Type: 2 wire, 115.2 kHz carrier
Baud Rate: 1,200 ASK or 9,600 FSK
Maximum Distance: 10,000 feet
Protocol: INCOM
Functions: Read/write set points
Read metered values
Read trip/alarms
Read events
Read history
Reset history
Reset functions
Emergency override
Trip
View starting prole

Log Book: 100 events
Log Event: 20 trips and alarms
Log Start: Last 4 starts
Start Prole: Last 4 starts (communications
port only)
History Records: Motor, trips, alarms, and totals

Operating Temperature: -20° to +60°C (-4° to +140°F)
Storage Temperature: -45° to +85°C (-49° to +185°F)
Humidity: 0 to 95% non-condensing

Height: 10.25 in. (26.04 cm)
Width: 6.72 in. (17.0 cm)
Depth: 4.3 in. (10.9 cm)
Weight: 4.0 lbs. (1.8 kg)
7.0 lbs. (3.2 kg) (with URTD
and PONI)

ANSI/IEEE C37.90-1989
Standard for Relay Systems Associated with Electric Power Apparatus.
ANSI/IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems
ANSI/IEEE C37.90.2-1995
Standard Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
UL-1053
Ground Fault Sensing and Relaying Equipment
Emissions (EN-50081-2):
EN 50011 CISPR-11, Class A, CFR 47 FCC Part 15
Subpart b Class A
EN-61000-6-2 Immunity
EN 61000-4-2 ESD
EN 61000-4-3 RF Radiated Immunity
EN 61000-4-4 EFT/Burst Immunity
EN 61000-4-5 Surge Immunity
EN 61000-4-6 RF Conducted Immunity
EN 61000-4-8 Power Frequency Magnetic Field Immunity
EN 61000-4-11 Voltage Variation Immunity