IM02602002E
Page 5-12
www.eaton.com
MP-3000
 
P13L7 is read-only - not a setting. Use this setting to determine if
Discrete Input 1 is ON (energized) or OFF.
 
P13L8 is read-only - not a setting. Use this setting to determine if
Discrete Input 2 is ON (energized) or OFF.

Page 14 is used to reset or clear the accumulated history mode statis-
tics on the History pages.
Press the line button on the History page to clear.
Press either Value button to get the PUSH RST display.
Press the Reset pushbutton to clear the History page.
To escape without clearing, do not push Reset. Use a Value
button to change from PUSH RST back to [History Page
Name] RST, then navigate elsewhere or exit the Program
Mode.
The four History pages are:
Setting P14L1, Motor History Reset (MTR RST);
Setting P14L2, Trip History Reset (TRIP RST);
Setting P14L3, Alarm History Reset (ALRM RST); and
Setting P14L4, History Totals Reset (TOT RST).
Refer to Section 4 for more information on the History Mode displays
that can be cleared.

Setting P15L1 is used to enable (on) or disable (off) the RS-232 com-
munications mode. Note that URTD and PONI communications are
disabled when in the RS-232 mode. Be sure that the PowerNet is set
to greater than 0; otherwise, the unit will not communicate.