IM02602002E
www.eaton.com Page 4-7
MP-3000
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
VALUE SELECTED
VIEW SP VIEW PROGRAM SETTINGS
1 FLA XXXX FULL LOAD AMPS
10-3,000 amps in 1 amp. increments
2 LRC XXXX LOCKED-ROTOR CURRENT % OF FLA
300-1,200% in 1% increments
3 LRT XXX MAXIMUM ALLOWABLE STALL TIME IN
SECONDS
1-120 sec. in 1 sec. increments
4 UTC XXX ULTIMATE TRIP CURRENT IN %FLA
85-150% in 1% increments
5 PCT XXXX PHASE CT RATIO NUMERATOR IN
PRIMARY AMP
10-4,000 A in increments of 1
6 GCT XXXX GROUND CT RATIO NUMERATOR IN
PRIMARY AMP
10-4,000 A in increments of 1
7 FREQ 50
or FREQ 60
50 - FOR 50 HERTZ LINE FREQUENCY
60 - FOR 60 HERTZ LINE FREQUENCY
Toggles between FREQ 50 and
8 REV or NON
REV
REVERSING OR NONREVERSING
STARTER
Toggles between REV and
9 STOP X MOTOR STOP CURRENT LEVEL IN
% OF PHASE CT RATIO NUMERATOR
2-20% of phase CT ratio numerator in 1%
increments
1 RTD IN °C
or
RTD in °F
DISPLAYED IN DEGREES °C OR °F
Toggles between °C and RTD IN °F
2 WD T XXX WINDING TEMP TRIP 0-199°C, OFF/32-390 °F, OFF in 1 increments
3 WD A XXX WINDING TEMP ALARM
0-199°C, OFF/32-390°F, OFF in 1 increments
4 MB T XXX MOTOR BEARING TRIP 0-199°C, OFF/32-390°F, OFF in 1 increments
5 MB A XXX MOTOR BEARING ALARM
0-199°C, OFF/32-390°F, OFF in 1 increments
6 LB T XXX LOAD BEARING TRIP
0-199°C, OFF/32-390°F, OFF in 1 increments
7 LB A XXX LOAD BEARING ALARM 0-199°C, OFF/32-390°F, OFF in 1 increments
8 AX T XXX AUXILIARY TRIP
0-199°C, OFF/32-390°F, OFF in 1 increments
9 AX A XXX AUXILIARY ALARM
0-199°C, OFF/32-390°F, OFF in 1 increments
10 DIAG ON
or
DIAG OFF
ALARM ON RTD FAILURE DIAGNOSTIC
Toggles between and DIAG OFF
1 GFT XXX GROUND FAULT TRIP LEVEL IN % OF
GROUND CT RATIO NUMERATOR
2-55% OF Ground CT ratio numerator, OFF
(1% increments)
Program Date Control Schematic
Unit ID/Starter Type Work Order #
Motor HP Mfgr. Serial # Volts
FLA LRC Stall Time/LRT Accel. Time
SF RTD Type Other