The MP-3000 declares a motor stop after about 20 cycles of no cur-
rent. The only way to extend this time is to assign the MOTOR STOP
function to one of the discrete inputs, and connect an external stop-
indicating contact. Refer to Subsection 5.6.1 for details.
If the ac supply returns after the stop declaration, but before the
MP-3000 microprocessor shuts down, the MP-3000 relay can go
through another start cycle and return to the RUN state without ever
tripping the motor. However, this on-the-y restart declaration won’t
happen if the relay has antibackspin or other jogging timer blocking in
effect. The relay trips at the moment the MP-3000 declares a stop.





-
-

-

