IM02602002E
Page 10-4
www.eaton.com
MP-3000

MP-3000
Setting
IQ 1000
II Setting
Setting Description
IQ 1000 II Range
(stay within these ranges to
communicate in IQ 2 EN mode)
MP-3000 Range
(stay within these ranges
to communicate in IQ 2
EN mode)
P2L2 3 Winding temperature trip 0-199°C (32-390°F) OFF
P2L4 4 Motor bearing temperature trip 0-199°C (32-390°F) OFF
P2L6 5 Load bearing temperature trip 0-199°C (32-390°F) OFF
P2L8 6 Auxiliary temperature trip 0-199°C (32-390°F) OFF
P2L3 7 Winding temperature alarm 0-199°C (32-390°F) OFF
P2L5 8 Motor bearing temperature alarm 0-199°C (32-390°F) OFF
P2L7 9 Load bearing temperature alarm 0-199°C (32-390°F) OFF
P2L9 10 Auxiliary temperature alarm 0-199°C (32-390°F) OFF
P3L1 11 Ground fault trip level 1-12 A OFF, .2-2,200 A
P3L2 12 Ground fault start delay 1-20 cycles 2-60 cycles
P3L3 14 Ground fault run delay 0-10 cycles 0-60 cycles
P3L5 16 IOC start delay 1-20 cycles 2-60 cycles
P1L3 18 Locked rotor time 1-60 seconds 1-120 seconds
P1L4 19 Ultimate trip current 85-125 85-150
P4L2 20 I2T alarm 60-100% OFF, 60-99%
P4L3 22 Jam alarm 100-1,200% of FLA OFF
P3L6 23 Jam trip 100-1,200% of FLA OFF
P3L7 24 Jam start delay 0-60 seconds 0-1,200 seconds
P3L10 28 Underload start delay 0-100 seconds 0-120 seconds
P3L11 29 Underload run delay 1-10 seconds 0-240 seconds
P4L7 30 Phase unbalance alarm 10-50% OFF, 4-40%
P5L5 37 Transition current 50-150% FLA 10-300% FLA
P5L6 38 Transition time 0-240 seconds 0-480 seconds
P5L8 40 Incomplete sequence time 1-60 seconds OFF, 1-240 seconds
P5L12 41 Antibackspin time 0-600 seconds (0 means OFF) OFF,1-3,600 seconds
P6L1 46 Program discrete input
REM RST, REM TRIP, DIF TRIP,
MTR STOP, RST DBL
EMG OVR, ZERO SW
P9L1
Through
P9L25
48 Trip state for AUX1 relay
All trips, IOC only, I2T only, GFLT
only, JAM only, UL only, MBT only,
LBT only, WT only, and REV only
Fully programmable—
over 4,194,304
possibilities, including
new load shed function