7
*. The maximum current can be obtained when the UPS input is 187V, output is under
rated full load, and charger works under full load.
*. When output voltage is adjusted from 220V to 200V or 208V, the rated power of output
VA and WATT should be decreased by 10%.
*. T h e o u tpu t v o lta g e i s a d jus t abl e a c cor d ing to cus tom e r r e qui rem e nts
(200/208/220/230/240 VAC).
Altitude (m) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Coefcient 100% 95% 91% 86% 82% 78% 74% 70% 67%
CAUTION: It needed to reduce the power of output when the products are used in a
high altitude above 1000m, the coefcient for the actual power refer to the foregoing
table.
Actual power (all Load capacity) = rated power * coefficient (correspond to the altitude)