What does it mean when Eaton 9PX 5000 says MBP disconnected?
- RRobert WilliamsSep 23, 2025
If the HotSwap MBP is no more connected to the Eaton UPS, check that the detection connector is correctly plugged if the HotSwap MBP is connected to the UPS.
 

What does it mean when Eaton 9PX 5000 says MBP disconnected?
If the HotSwap MBP is no more connected to the Eaton UPS, check that the detection connector is correctly plugged if the HotSwap MBP is connected to the UPS.
What does it mean when the battery fault LED is on and Eaton 9PX 5000 beeps continuously?
This indicates that the battery test failed due to bad or disconnected batteries, or the battery minimum voltage has been reached in ABM cycling mode. Verify that all batteries are properly connected. Start a new battery test; if the condition persists, contact your service representative.
Why is the battery mode LED on and Eaton 9PX 5000 beeping every 10 seconds?
A utility failure has occurred, and the UPS is in Battery mode. The UPS is powering the equipment with battery power; prepare your equipment for shutdown.
What does it mean when the battery low LED is on and Eaton 9PX 5000 beeps every 3 seconds?
The UPS is in Battery mode, and the battery is running low. This warning is approximate, and the actual time to shutdown may vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the 'Battery Low' warning may occur before the batteries reach 20% capacity.
What to do if no battery LED is on and Eaton 9PX 5000 UPS beeps continuously?
The batteries are disconnected. Verify that all batteries are properly connected. If the condition persists, contact your service representative.
What to do if the input bad wiring / output bad wiring LED is on for Eaton UPS?
If the Eaton UPS input/output cables are not connected to the correct terminal blocks, connect correctly the Input/Output cables.
Why is the bypass mode LED on on my Eaton UPS?
If an overload or a fault has occurred, or a command has been received and the Eaton UPS is in Bypass mode, equipment is powered but not protected by the UPS. Check for one of the following alarms: overtemperature, overload or UPS failure.
How to troubleshoot an Eaton 9PX 5000 that does not start?
If the Eaton UPS does not start because the input source is not connected correctly, check the input connections. If the UPS does not start because the Remote Power Off (RPO) switch is active or the RPO connector is missing, inactivate the RPO input if the UPS Status menu displays the 'Remote Power Off' notice.
What to do if the MBP is disconnected from my Eaton 9PX 5000?
The HotSwap MBP is no more connected to the UPS. If the HotSwap MBP is connected to the UPS, check that the detection connector is correctly plugged.
Why is the bypass mode LED on my Eaton 9PX 5000?
An overload or a fault has occurred, or a command has been received and the UPS is in Bypass mode. This means your equipment is powered but not protected by the UPS. Check for one of the following alarms: overtemperature, overload or UPS failure.
| Power Rating | 5000 VA / 4500 W | 
|---|---|
| Dimensions (H x W x D) | 3.5 x 17.5 x 21.3 in | 
| Weight | 103 lbs | 
| Form Factor | Rack/Tower | 
| Warranty | 2 years | 
| Input Voltage | 200-240 VAC | 
| Output Voltage | 200/208/220/230/240 VAC | 
| Output Frequency | 50/60 Hz | 
| Battery Type | Sealed lead-acid battery | 
| Communication | USB | 
| Runtime at Half Load | Approx. 10-15 minutes (varies by battery configuration) | 
| Topology | Double Conversion Online | 
| Typical Backup Time | approximately 15 minutes at half load | 
Details precautions for handling personnel and avoiding electrical hazards.
Outlines installation and operational safety guidelines for the UPS unit.
Covers handling, lifting, and battery replacement safety measures for the unit.
Explains how to connect Extended Battery Modules (EBMs) to the UPS.
Provides instructions for mounting the UPS in a 19-inch rack.
Specifies upstream protection and cable cross-section requirements.
Details the procedure for connecting input and output power cables by qualified personnel.
Guides on how to safely start up and shut down the UPS unit.
Describes the UPS's Online, Battery, Bypass, and Standby operating modes.
Explains automatic battery tests, low battery warnings, and deep discharge protection.
Describes the feature for remotely shutting down the UPS and load.
Advises on when to replace UPS batteries based on screen prompts.
Explains the procedures and precautions for replacing UPS batteries.
Presents a chart of common UPS alarms, their causes, and recommended actions.