ENGLISH
9PX 6K SP
9PX EBM 240V SP
Installation
and user manual
Copyright © 2013 EATON
All rights reserved.
Service and support:
Call your local service representative
9PX6K-SP_EN

Questions and Answers

  • A
    Alexander RodriguezAug 14, 2025
    What to do if the power overload LED is on and the Eaton 9PX 6K SP beeps continuously?
    • I
      ivaughnAug 14, 2025
      If the power requirements exceed the UPS capacity, remove some equipment from the Eaton UPS. The UPS will continue to operate, but may switch to Bypass mode or shut down if the load increases. The alarm resets when the condition becomes inactive.
  • J
    Jennifer DavisAug 17, 2025
    Why is the battery mode LED on and the Eaton 9PX 6K SP UPS beeping every 10 seconds?
    • H
      Hannah MoranAug 17, 2025
      A utility failure has occurred, and the Eaton UPS is running in Battery mode. The UPS is powering your equipment with battery power, so prepare your equipment for shutdown.
  • A
    Angela HarperAug 20, 2025
    Why doesn't my Eaton UPS provide the expected backup time?
    • K
      Karl RobinsonAug 20, 2025
      The batteries may need charging or servicing. Apply utility power for 48 hours to charge the batteries. If the problem persists, contact your service representative.
  • M
    matthewhallAug 25, 2025
    What to do if the Eaton 9PX 6K SP UPS overtemperature LED is on and beeping?
    • J
      Justin OliverAug 25, 2025
      The UPS internal temperature is too high or a fan has failed. If the UPS transferred to Bypass mode, it will return to normal operation when the temperature drops 5°C below the warning level. If the condition persists, shut down the UPS, clear vents, remove any heat sources, and ensure airflow is not restricted. Restart the UPS, and if the condition continues, contact your service representative.
  • C
    Christine AllenAug 27, 2025
    Why is the bypass mode LED on for my Eaton UPS?
    • C
      Corey WaltersAug 27, 2025
      An overload or fault has occurred, or a command has been received, and the UPS is in Bypass mode. This means your equipment is powered but not protected by the UPS. Check for overtemperature, overload, or UPS failure alarms.
  • P
    pdanielsAug 30, 2025
    What does it mean when the battery fault LED is on and the Eaton UPS beeps continuously?
    • D
      Debbie WilsonAug 31, 2025
      The battery test has failed due to bad or disconnected batteries, or the battery minimum voltage is reached in ABM cycling mode. Verify that all batteries are properly connected and start a new battery test. If the condition persists, contact your service representative.
  • J
    John NormanSep 3, 2025
    Why does my Eaton 9PX 6K SP UPS not start?
    • A
      Alexander DennisSep 3, 2025
      The input source may not be connected correctly, so check the input connections. Alternatively, the Remote Power Off (RPO) switch may be active, or the RPO connector is missing. If the UPS Status menu displays the 'Remote Power Off' notice, inactivate the RPO input.
  • R
    Randy LarsonSep 6, 2025
    What does it mean when no battery LED is on and the Eaton 9PX 6K SP beeps continuously?
    • S
      Sherry WatkinsSep 6, 2025
      The batteries are disconnected. Verify that all batteries are properly connected. If the condition persists, contact your service representative.
  • B
    Brittany LawrenceSep 9, 2025
    What to do if the input/output bad wiring LED is on and the Eaton 9PX 6K SP UPS is beeping continuously?
    • J
      Julia TurnerSep 9, 2025
      The input/output cables are not connected to the correct terminal blocks. Connect the input/output cables correctly.

Summary

Safety Instructions

Certification Standards

Lists compliance standards for safety and EMC.

Special Symbols

Explains common symbols used in the manual for warnings and information.

Safety of Persons

Details safety precautions related to personnel handling the UPS and its components.

Product Safety

Outlines safety guidelines for the UPS installation and operation.

Special Precautions

Provides specific handling and operational advice for safe use of the UPS.

Introduction

Environmental Protection

Details Eaton's environmental policy and product eco-design approach.

Presentation

Weights and Dimensions

Provides physical specifications for the UPS and Extended Battery Modules.

Rear Panel Layout

Identifies and describes the ports and connectors on the rear of the UPS unit.

Optional Accessories

Lists optional accessories available for the UPS system.

9 PX 6 K SP Installation

Equipment Inspection and Unpacking

Guides on checking for shipping damage and safely unpacking the UPS unit.

Accessory Kit Verification

Lists and verifies the contents of the UPS accessory kit.

Tower and Rack Installation

Details the procedures for installing the UPS in tower and rack configurations.

Internal Battery Connection

Provides instructions for connecting the UPS's internal battery pack.

EBM Installation

EBM Inspection and Unpacking

Guides on checking for shipping damage and safely unpacking the Extended Battery Module.

EBM Accessory Kit Verification

Verifies the contents of the accessory kit for the Extended Battery Module.

EBM Preparation and Installation

Details steps for preparing the EBM, including battery removal, and rack mounting.

EBM Tower Installation

Explains the procedure for installing the EBM in a tower configuration.

Connecting EBMs and Accessories

Guides on connecting Extended Battery Modules and other optional accessories to the UPS.

Power Cable Connection

Installation Requirements

Specifies requirements for upstream protection and cable cross-sections for power connection.

Terminal Blocks and Wiring

Details how to access terminal blocks and perform hardwired input/output connections.

HMI and Settings

Control Panel Overview

Describes the UPS's graphical LCD and its five-button interface.

LCD Description and Operation Status

Explains the UPS operating status indicators and screen saver functionality.

Display Functions and User Settings

Details menu functions for measurements, control, logs, and user-configurable settings.

Operation

UPS Startup and Shutdown

Provides step-by-step instructions for starting and shutting down the UPS.

Operating Modes

Explains the different operational states of the UPS, including Online, Battery, Bypass, and High Efficiency.

Mode Transfers and Battery Settings

Covers transferring UPS between modes and configuring bypass and battery settings.

Event and Fault Log Retrieval

Guides on accessing and reviewing the UPS's event and fault logs.

Communication

Communication Ports and Remote Control

Describes RS232/USB ports, relay outputs, Remote On/Off, and Remote Power Off capabilities.

Connectivity Cards

Lists and describes available communication cards for networking and monitoring.

Eaton Intelligent Power Software Suite

Introduces the software suite for UPS management and monitoring.

UPS Maintenance

Equipment Care and Storage

Provides guidelines for maintaining the UPS cleanliness, environment, and proper storage.

Battery Replacement

Explains when and how to replace UPS batteries.

EBM Replacement and Battery Testing

Details procedures for replacing Extended Battery Modules and testing new batteries.

Recycling Used Equipment

Offers guidance on the proper disposal and recycling of UPS and battery components.

Troubleshooting

Typical Alarms and Faults

Presents a chart of common UPS alarms, their causes, and recommended actions.

Alarm Silencing and Service

Describes how to silence alarms and provides information for contacting service and support.

Specifications

Model and Electrical Specifications

Lists model details, weights, dimensions, and electrical input/output parameters.

Glossary

Eaton 9PX 6K SP Specifications

General IconGeneral
Power Rating6000 VA / 5400 W
TopologyDouble Conversion Online
Typical Recharge Time3 hours to 90%
Form FactorTower
Operating Temperature0 to 40 °C
Humidity0-95% relative humidity, non-condensing
Warranty2 years
Output Power Factor0.9
Input Voltage200-240 VAC
Output Voltage200/208/220/230/240 VAC
Battery TypeSealed Lead Acid
Communication PortsUSB, RS-232
Storage Temperature-15°C to 45°C (5°F to 113°F)
CertificationsCE
Output Receptacles1 x IEC 320 C19
EfficiencyUp to 94% in online mode, up to 98% in high-efficiency mode